Exclusive limit alarm¶
Properties¶
Name |
BrowseName |
DataType |
Description |
---|---|---|---|
High-high limit | HighHighLimit |
High-high limit value
(Inherited from Limit alarm)
|
|
High limit | HighLimit |
High limit value
(Inherited from Limit alarm)
|
|
Low limit | LowLimit |
Low limit value
(Inherited from Limit alarm)
|
|
Low-low limit | LowLowLimit |
Low-low limit value
(Inherited from Limit alarm)
|
|
Enabled | Enabled |
Enable/disable the alarm.
(Inherited from Alarm controller)
|
|
Auto acknowledge | AutoAcknowledge |
True: when the alarm activates, it is automatically acknowledged and confirmed. False: when the alarm activates, it must be acknowledged by the user.
(Inherited from Alarm controller)
|
|
Auto confirm | AutoConfirm |
True: when the alarm activates, it is automatically confirmed by the application. False: when the alarm activates, it must be confirmed by the user.
(Inherited from Alarm controller)
|
|
Input variable | InputValue |
Variable to monitor
(Inherited from Alarm controller)
|
|
Message | Message |
Alarm message text
(Inherited from Alarm controller)
|
|
Severity | Severity |
Level of severity of the alarm, which indicates its priority on a scale from 1 to 1000 (in compliance with the OPC UA standard: 1 = information, 1000 = serious error).
(Inherited from Alarm controller)
|
|
Last event | LastEvent |
Last alarm event generated
(Inherited from Alarm controller)
|