Limit alarm¶
BrowseName: LimitAlarmController
SuperType: Alarm controller (AlarmController)
Monitors when the values of interest are reached for variables relating to physical quantities. Activates when the value of the monitored variable reaches one or more limits of interest. When several limits of interest are reached consecutively, the alarm signals only the last limit reached (exclusive) or all the limits reached (non-exclusive).
Properties¶
Name |
BrowseName |
DataType |
Description |
---|---|---|---|
High-high limit | HighHighLimit |
High-high limit value |
|
High limit | HighLimit |
High limit value |
|
Low limit | LowLimit |
Low limit value |
|
Low-low limit | LowLowLimit |
Low-low limit value |
|
Enabled | Enabled |
Enable/disable the alarm.
(Inherited from Alarm controller)
|
|
Auto acknowledge | AutoAcknowledge |
True: when the alarm activates, it is automatically acknowledged and confirmed. False: when the alarm activates, it must be acknowledged by the user.
(Inherited from Alarm controller)
|
|
Auto confirm | AutoConfirm |
True: when the alarm activates, it is automatically confirmed by the application. False: when the alarm activates, it must be confirmed by the user.
(Inherited from Alarm controller)
|
|
Input variable | InputValue |
Variable to monitor
(Inherited from Alarm controller)
|
|
Message | Message |
Alarm message text
(Inherited from Alarm controller)
|
|
Severity | Severity |
Level of severity of the alarm, which indicates its priority on a scale from 1 to 1000 (in compliance with the OPC UA standard: 1 = information, 1000 = serious error).
(Inherited from Alarm controller)
|
|
Last event | LastEvent |
Last alarm event generated